Application:
JGG cables are vital elements for wind converters, MV AC drives,transformers, solar power inverters and other MV/LV cabinets. In drives, silicone decreases copper cross-section and gives flexibility for compactness. This product family is fit for frequency converter power transmission system with high temperature resistant.
Cross- section | Conductor | Insulation | Outer diameter | Max resistance at 20ºC | |||||||
11KV | 12KV | 11KV | 12KV | ||||||||
Conductor construction No./D | Diameter
| Nominal thickness | Minimum thickness | Nominal thickness | Minimum thickness | Nominal outer diameter | Tolerance | Nominal outer diameter | Tolerance | Ω/km | |
mm2 | No./mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | under |
6 | 84/0.30 | 3.30 | 5.80 | 5.12 | 6.90 | 6.11 | 14.90 | ±0.30 | 17.10 | ±0.30 | 3.39 |
10 | 84/0.39 | 4.60 | 5.80 | 5.12 | 6.90 | 6.11 | 16.20 | ±0.30 | 18.40 | ±0.30 | 1.95 |
16 | 126/0.40 | 5.70 | 6.00 | 5.30 | 7.10 | 6.29 | 17.70 | ±0.30 | 19.90 | ±0.30 | 1.24 |
25 | 196/0.40 | 7.10 | 6.00 | 5.30 | 7.10 | 6.29 | 19.10 | ±0.40 | 21.30 | ±0.40 | 0.795 |
35 | 276/0.40 | 8.50 | 6.20 | 5.48 | 7.30 | 6.47 | 20.90 | ±0.40 | 23.10 | ±0.40 | 0.565 |
50 | 396/0.40 | 10.00 | 6.50 | 5.75 | 7.60 | 6.74 | 23.00 | ±0.40 | 25.20 | ±0.40 | 0.393 |
70 | 558/0.40 | 11.80 | 6.70 | 5.93 | 7.80 | 6.92 | 25.20 | ±0.50 | 27.40 | ±0.50 | 0.277 |
95 | 756/0.40 | 13.60 | 6.70 | 5.93 | 7.80 | 6.92 | 27.00 | ±0.50 | 29.20 | ±0.50 | 0.210 |
120 | 956/0.40 | 15.20 | 7.30 | 6.47 | 8.20 | 7.28 | 29.80 | ±0.50 | 31.60 | ±0.50 | 0.164 |
150 | 1194/0.40 | 17.20 | 7.30 | 6.47 | 8.20 | 7.28 | 31.80 | ±0.50 | 33.60 | ±0.50 | 0.132 |
185 | 1473/0.40 | 19.00 | 7.70 | 6.83 | 8.40 | 7.46 | 34.40 | ±0.50 | 35.80 | ±0.50 | 0.108 |
240 | 1910/0.40 | 21.70 | 7.90 | 7.01 | 8.60 | 7.64 | 37.50 | ±0.50 | 38.90 | ±0.50 | 0.0817 |
300 | 2388/0.40 | 24.30 | 8.00 | 7.10 | 8.80 | 7.82 | 40.30 | ±0.50 | 41.90 | ±0.50 | 0.0654 |